Physical Properties Temperature ion) 68 - 77 F (can) or min. +41 F (surfaces)
Track free time Depending on the humidity and temp 5 to 10 min
Cut time Depending on Humidity and temp 15 to 20 min
Hardening time Depending on Humidity and temp 5 to 12 hours
Absorption (water) 2% volume max
Temperature - 40 to + 210 F
Strength (tensile) 0,071 to 0,076 MPa
Elongation at break 15 to 20%
Flammability Class B1 according to DIN 4102, part 1
Storage Nine months at +50 F to +68 F, the can should be placed vertical. Higher temps can cause less life expectancy of the can
Abesco FP200 FR Expanding Foam has been tested in various countries in accordance with the methodology and criteria described in:
• ASTM E814 / UL 1479 (1 & 2 Hr)
• ASTM E-84 (Flame 10, Smoke 35)
• ASTM E-662
• ASTM E-162
• BS 476- 20 (up to 4 Hr)
• EN 1366-3 (up to 4 Hr)
/Asset/fp200-1.jpg
FBC System Compatible* indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold®, BlazeMaster® and Corzan pipe and fittings.
FlowGuard Gold®, BlazeMaster® and Corzan® are licensed trademarks of Lubrizol Corporation.
/Asset/Metacaulk_1000.jpg
FBC System Compatible* indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold®, BlazeMaster® and Corzan pipe and fittings.
FGG/BM/CZ,FlowGuard Gold®, BlazeMaster® and Corzan® are licensed trademarks of Lubrizol Corporation.
/Asset/Metacaulk_redpipecollars.jpg
![FP200 FP200](/ImgSmall/fp200-1.jpg)
Firestop Foam
(2) Abesco FP200 FR Expanding Foam is a single pack Fire Rated polyurethane expanding foam, and is designed to prevent the spread of fire and smoke from one compartment to another through gaps and voids through fire rated walls or floors![Metacaulk® MC 150+ Metacaulk® MC 150+](/ImgSmall/Metacaulk_150+.jpg)
Metacaulk® MC 150+ Fire Stop
Metacaulk® MC 150+ is a one component, general purpose fire-rated sealant and smoke seal for construction joints and through-penetrations. It prevents the spread of flames, smoke, and gas through penetration openings. Metacaulk® MC 150+ is a water based, non-sag caulking grade sealant that is easy to apply as well as to retrofit. Metacaulk® MC 150+ can be used on various penetrations such as top of the wall construction joints, deflection track wall systems, EMT, telephone and power cables in concrete floors and walls, gypsum walls as well as wood floors. Metacaulk? MC 150+ may be applied with a caulking gun or trowel. For large applications, it may be pumped from the pail. Metacaulk® MC 150+ cures to an elastomeric seal that is suitable where dynamic movement is expected. Sound Transmission Class (STC) Rating 51*. *Tested in a UL 411 wall assembly/section to ASTM E90. /Asset/Metacaulk_150+.jpg![Metacaulk® 350i Metacaulk® 350i](/ImgSmall/Metacaulk_350i3.jpg)
Metacaulk® 350i
Metacaulk® 350i is a one-component, general purpose fire-rated sealant and smoke seal for construction joints and through-penetrations. Metacaulk® 350i is an intumescent, water-based, non-sag caulking grade sealant that is easy to apply and great for retrofits. It cures to an elastromeric seal that is suitable where dynamic movement is expected. Sound Transmission Class (STC) rating 53, Tested in a UL 411 wall assembly/section to ASTM E90. /Asset/Metacaulk_350i3.jpg![Metacaulk® 1000 Metacaulk® 1000](/ImgSmall/Metacaulk_1000.jpg)
Metacaulk® 1000Intumescent (Red)Premium
Metacaulk® 1000 is a water based, single-component, general purpose, fire-rated sealant for through-penetrations on both vertical and horizontal surfaces, as well as construction joints. It is designed for use in floors or walls and can be used on PVC, CPVC, ABS, PVC foam core, ABS foam core, PP or plastic pipes, polybutylene (PB), insulated and uninsulated steel pipe, copper and cast iron. Sound Transmission Class (STC) Rating 54*. Complies to Required Environmental Exposure Testing of Accelerated Aging and High Humidity as per UL 1479 Fire Test of Through-Penetration Firestops. U.S. Patent No. 6,207,085. *Tested in a UL 411 wall assembly/section to ASTM E90.![Metacaulk® 1200 Metacaulk® 1200](/ImgSmall/Metacaulk_1200.jpg)
Metacaulk® 1200Sprayable Fire Stop Mastic
Metacaulk® 1200 is a water-based firestop sealant that comes in three different grades and 2 colors: red and an easy-to-paint white. A spray application of Metacaulk® 1200 provides a fast, economical means of installation for long joint runs. Self Leveling is made for horizontal applications and caulk grade is a non-sag sealant that is easy to apply. Metacaulk® 1200 is also an excellent, fire-rated acoustical sealant. It cures to an elastomeric membrane seal suitable for use where dynamic movement is expected. Sound Transmission Class (STC) Rating 50*. *Tested in a UL 411 wall assembly/sectio /Asset/Metacaulk_1200.jpg![Metacaulk® pipe collars Metacaulk® pipe collars](/ImgSmall/Metacaulk_redpipecollars.jpg)
Metacaulk® Pipe Collars
Metacaulk® Pipe Collars are prefabricated for through-penetration firestop systems using PVC, CPVC, ABS, PVC foam core, ABS foam core, FRPP, PEX pipe and electrical cable. Designed to reduce installation time by 25% and the simple locking mechanism insures easy installation. Metacaulk® Pipe Collars are economical because no backfill is usually required. UL Classified for both open and closed pipe systems. Complies to Required Environmental Exposure Testing of Accelerated Aging and High Humidity as per UL 1479 Fire Test of Through-Penetration Firestops. U.S. Patent No. 6,207,085.![Metacaulk® pillow Metacaulk® pillow](/ImgSmall/Metacaulk_pillow.jpg)
Metacaulk® Firestop Pillows
Metacaulk® Firestop Pillows are intumescent and designed for use primarily in large openings with cables, cable trays, blank openings or multiple penetrating items. /Asset/Metacaulk_pillow.jpg![Cover Guard Cover Guard](/ImgSmall/cover guard.jpg)
Metacaulk® Cover Guard™i
Metacaulk® Cover Guard™is a single component fire rated gasket for use with electrical boxes when addressing the "24 inch rule". Metacaulk® Cover Guard™ is applied by hand, does not take up volume in the electrical box and is a labor saving replacement for putty pads in normal applications. Sound Transmission Class (STC) Rating 54*. Complies to Required Environmental Exposure Testing of Accelerated Aging and High Humidity as per UL 1479 Fire Test of Through-Penetration Firestops. U.S. Patent No. 6,207,085 & 6,252,167. *Tested in a UL 411 wall assembly/section to ASTM E90. /Asset/cover guard.jpg![Metacaulk® joint strip Metacaulk® joint strip](/ImgSmall/Metacaulk_jointstrips.jpg)
Metacaulk® Joint Strip
Metacaulk® Joint Strip is a flexible, highly intumescent firestop material used in concrete and masonry control joints up to 1" wide. It forms a strong char that prevents the passage of flame, smoke and hot gases between control joints. Metacaulk® Joint Strips are ideal for stadium construction, tilt up panels, curtain wall panels and all vertical concrete and masonry construction joint applications where a fire rated control joint is required. Complies to Required Environmental Exposure Testing of Accelerated Aging and High Humidity as per UL 1479 Fire Test of Through-Penetration Firestops /Asset/Metacaulk_jointstrips.jpg![Metacaulk® composite sheet Metacaulk® composite sheet](/ImgSmall/Metacaulk_compsite_sheet.jpg)
Metacaulk® Composite Sheet
Metacaulk® Composite Sheet is a rigid fire resistive panel used to seal penetrations and restore the fire rating to floor/ceilings or walls in which a large opening has been made for the passage of penetrating items. /Asset/Metacaulk_compsite_sheet.jpg![Metacaulk® Box Guard Metacaulk® Box Guard](/ImgSmall/Metacaulk_boxgaurd.jpg)
Metacaulk® Box Guard™
Metacaulk® Box Guard™ is a one component fire rated pad for use in electrical boxes. It is inserted on the inside back wall of an electrical box and is a highly intumescent firestop material. Saves labor costs. Box Guard™ is an economical alternative to putty pads. Great for use on retrofit jobs. Sound Transmission Class (STC) Rating 53*. Complies to Required Environmental Exposure Testing of Accelerated Aging and High Humidity as per UL 1479 Fire Test of Through-Penetration Firestops. U.S. Patent No. 6,207,085 & 6,252,167. *Tested in a UL 411 wall assembly/section to ASTM E90 /Asset/Metacaulk_boxgaurd.jpg![PuttPads PuttPads](/ImgSmall/Metacaulk_puttypads.jpg)
Metacaulk® Putty Pads
Metacaulk® Putty Pads are used to maintain the hourly rating of fire rated walls containing electrical outlet boxes and to reduce sound transmission. Only one pad thickness (1/8) inch is required for a 1 or 2 hour fire rating. No additional putty material is needed to plug the end of each electrical metallic tube or conduit at its connection to the box. Sound Transmission Class (STC) Rating 60*. *Tested in a UL 411 wall assembly/section to ASTM E90 /Asset/Metacaulk_puttypads.jpg![Metacaulk Pass Thru2 Metacaulk Pass Thru2](/ImgSmall/passthru.jpg)